Pre-insertion Resistor and Grading Capacitor in Multi Break Circuit Breaker


Two types of Circuit Breakers are used in 400 kV Switchyard. They differ in only one features i.e. Pre Insertion Resistor (PIR). One type has PIR whereas other has no such provision. Both type of breaker are self-compensating Spring to Open and Spring to Close type. SF6 gas is used as arc quenching medium. The normal pressure of SF6 gas is 6 bar(g).

Figure below shows a typical Grading Capacitor used in Double Break Circuit Breaker.



Purpose of PIR:

PIR is pre-insertion-resistor. This is a resistor of about 200-400 ohms which gets temporarily closed before closing the circuit breaker. The sequence is (close order)->closing of PIR->10-12milliseconds->closing of main break.

But while opening, PIR is first disconnected by the Breaker operating mechanism and then i.e. after 10 ms, main contacts of Breaker are opened. The main purpose of PIR is to limit the initial charging current of line. As the charging current of long line will be much more, it is advisable to use Breaker having PIR in long transmission line.

When electrical circuit having capacitance or transformer which can have inrush. Also transformers may have large inrush current. Transmission line (due to its capacitance) is another such circuit.



For closing in such circuit first the PIR comes in circuit to limit the inrush current. When the main contacts close, the current through PIR becomes zero as the shunt path is bridged by main contact.

Purpose of Grading Capacitor:

The purpose of grading capacitors is to ensure uniform voltage distribution in open position. If you mind, the pressure of SF6 gas kept in Breaker of 220 kV Switchyard is 6 bar and that used in 400 kV is also 6 bar. How could this be possible? Assuming that the gap between the main contacts of Breakers used in 220 kV and 400 kV Switchyard are same, when we increased the voltage the pressure of SF6 should also be increased as the Dielectric Breakdown strength of SF6 is proportional to its pressure.




Thing is that when we use Grading Capacitor, the voltage across each contact is distributed uniformly. Thus for Breaker having two contacts i.e. for Double Break Circuit Breaker, the voltage across each contact will be 200 kV and thus 6 bar of SF6 will work fine.

Thank you!